EAST stock code: 300376

EA900RT G4 10kVA-20kVA (1:1/3:1)

Characteristics Technical Specifications Documents

● High frequency on-line double conversion technology

● Advanced DSP and 3-level technology

● Output power factor 1.0

● Active power factor correction (APFC), input power factor up to 0.99

● High efficiency 95% (up to 98% in ECO mode)

● Advanced digital parallel technology

● 3:1 to 1:1 model settable

● Wide input voltage range (190 ~ 478 Vac) and frequency range (40 ~ 70 Hz)

● 50 / 60 Hz frequency auto sensing

● Two modes of frequency conversion: 50 Hz input / 60 Hz output or 60 Hz input / 50 Hz output

● Dual-input design, supporting independent bypass

● Hot-swappable battery (10 kVA)

 Flexible battery configuration (settable 16 - 20 pcs batteries)

 Digitally controlled charger

● High charging current available (Max. 10 A )

● Charging voltage and current configured by demands

● Linear derating in low voltage input reducing battery discharging times, extending the service life of battery

● Intelligent battery management, automatic floating / equalizing charge control, charger dormancy control, increasing battery life by 50%

● Ability to switch on the UPS with batteries

● Settable delayed start time when mains power is restored, reducing the impact on power grid or generator

● Fan speed varies intelligently with temperature, reducing noise and extending its service life

● Equipped with self-aging function

● Compact internal layout, miniaturized the complete unit for small footprint

● LCD+LED display, multi-functional keys operation, friendly human-machine interface

● Powerful background software for parameters configuration

● Advanced multi-platform communications: RS232, USB, RS485, SNMP and dry contacts communication interfaces

● Effective software and hardware protection function, robust self-diagnostic function, and abundant event log for check



Available Options

● RS232 and smart card slot included

● Optional parallel function, battery temperature compensation, SNMP card, USB, RS485 card, dry contacts, EMD, and SMS alarms


                MODEL                EA9010RT (3:1)                EA9015RT (3:1)
                EA9020RT (3:1)
                Capacity
                10 kVA / 10 kW
                15 kVA / 15 kW
                20 kVA / 20 kW
                INPUT
                Input wiring
                Three-phase five-wire (3Φ + N + PE)
                Rated voltage
                380 / 400 / 415 Vac
                Voltage range
                190 ~ 304 Vac (linear derating between 50% and 100% load); 304 ~ 478 Vac (no derating)
                Rated frequency
                Voltage range
                Frequency range
                40 ~ 70 Hz
                Power factor
                ≥ 0.99
                Bypass voltage range
                - 40% ~ +15% (settable)
                Total harmonic distortion (THDI)
                ≤ 5%
                OUTPUT
                Output wiring
                Single-phase (L-N)
                Rated voltage
                208 (PF=0.9) / 220 / 230 / 240 Vac
                Voltage regulation
                ± 1%
                Frequency
                Synchronized to bypass in mains mode; 50 / 60 Hz ± 0.1% Hz in battery mode
                Waveform
                Sinusoidal
                Power factor
                1
                Total harmonic distortion (THDV)
                ≤ 1% (linear load); ≤ 3% (non-linear load)
                Crest factor
                3:1
                Overload
                102% ~ 110% for 10 min, 110% ~ 125% for 1 min,125% ~ 150% for 30 s
                BATTERIES
                DC voltage
                192 Vdc (192 ~ 240 Vdc settable)

                    Number of battery


                16 pcs (16 ~ 20 settable)

                    Inbuilt battery (standard model)

                12 V / 9 Ah × 16
                /                /
                Charging current

                    Standard model: 1 A; 

                    Long time model: 5 A (default),1 ~ 5 A settable; 10 A (optional)

                Recharge time

                                      Standard model: 1 A;

                                      Long time model: 5 A (default),1 ~ 5 A settable; 10 A (optional)

                SYSTEM
                Efficiency                ≥ 94% at 100% load, max. 95% at 60% load, ≥ 98% in ECO mode
                Transfer time
                0 ms
                Protections
                Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
                Max. number of parallel connections
                4
                Communications
                RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)
                Display
                LCD + LED
                OTHERS
                Operating temperature
                0℃ ~ 40℃
                Storage temperature
                -25℃ ~ 55℃ (without battery)
                Relative humidity
                0 ~ 95% (non-condensing)
                Altitude
                ≤ 1000 m, derating 1% for each additional 100 m
                IP rating
                IP 20
                Noise level at 1 m
                ≤ 58 dB    
                Dimensions (W × D × H) (mm)

                    440 × 650 × 88 (H)

                    440 × 660 × 176 (S)
                440 ×780 × 132
                Packaged dimensions (W × D × H) (mm)

                    514 x 696 x 168 (H)

                    554 x 792 x 418 (S)

                554 x 792 x 400
                Net weight (kg)
                17 (H), 67 (S)
                25.5
                Gross weight (kg)
                19 (H), 77 (S)
                28

                      ● S means standard model, H means long time model.

                      ● All specifications subject to change without notice.


EA900RT G4 10kVA ~ 20kVA (3:1 / 1:1) User Manual - PDF

EA900RT G4 10kVA ~ 20kVA (3:1 / 1:1) Datasheet - PDF

 