EAST stock code: 300376

Off-Grid Solar Inverter 10 kVA - 120 kVA (3:3)

Characteristics Technical Specifications Documents

● High-speed DSP digital control

● Full-bridge inverter control technology, providing secure power supply in the event of threephase 100% unbalanced loads

● Multi-string PV connected

● Inbuilt AC rectifier and MPPT control modules, configured battery parameters by operating interface, self-regulation for charging voltage and current

● Hot-swap MPPT modules for easy maintenance and power expansion

● Auto access MPP tracking states, be most probable to use PV energy in priority

● Intelligent AC and PV complementation power supply function to extend the battery life

● Using multicore control technology and auto MPP trackers, auto-start AC rectifier enable PV and AC source to supply power to the loads at the same time in the event of insufficient PV, which reduces battery discharge times and extend the battery life

● Intelligent staggering power consumption function

● Standard RS232, RS485 and optional SNMP communication port

● Multiple remote control: startup, shutdown, abnormal clearance, EPO, battery test and remote alarm port

● Staggering energy storage and power generation


MODEL 10 kVA 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
Rated power
9 kW 18 kW 27 kW 36 kW 54 kW 72 kW
90 kW 108 kW
Rated current
15 A
30 A
45 A
60 A 91 A 120 A 152 A 182 A
Output power factor
0.9
Rated input voltage
380 Vac ± 20%
Rated output voltage
380 Vac± 1%
Battery voltage
360 Vdc
Number of battery
12 Vdc × 30 pcs / 2 Vdc × 180 pcs
Operating mode
AC and PV complementation
PV INPUT
Max. voltage (Voc)
750 Vdc
Optimum operating voltage (Vmp)
450 ~ 550 Vdc
Max. conversion efficiency
≥ 98%
Floating charge voltage (25℃)
414 Vdc ± 1%
Equalizing charge voltage (25℃)
428 Vdc ± 1%
MPPT Max. current
60 A
120 A
180 A
240 A
300 A
360 A
Max. PV power
25 kW
2 × 25 kW
3 × 25 kW
4 × 25 kW
5 × 25 kW
6 × 25 kW
Number of PV input
1 + 1 (reserved)
2 + 1 (reserved)
3 + 1 (reserved)
4 + 2 (reserved)
5 + 3 (reserved)
6 + 2 (reserved)
MPPT modules
1 + 1 (reserved)
2 + 1 (reserved)
3 + 1 (reserved)
4 + 2 (reserved)
5 + 3 (reserved)
6 + 2 (reserved)
AC RECTIFIER
Input voltage range
380 V ± 20% three-phase
Rated frequency
50 Hz / 60 Hz ± 5 Hz (settable)
Power factor
0.8
Floating charge voltage (25℃)
410 Vdc ± 1%
Floating charge voltage (25℃)
415 Vdc ± 1%
Max. charging current
20 A
40 A 60 A 80 A 120 A 160 A 200 A 240 A
INVERTER
Inverter voltage
380 Vac three-phase + N+PE
Phase voltage
220 / 230 / 240 Vac (settable)
Output voltage precision
± 1%
Transient voltage range
± 5%
Transient recovery time
20 ms
Rated frequency
50 Hz / 60 Hz ± 1 Hz (settable)
Frequency tracking range
50 Hz / 60 Hz ± 3 Hz
Peak factor
3:1
Waveform
Sinusoidal
Waveform distortion
≤ 3% (linear load)
Voltage unbalance
± 3% (100% unbalanced load)
Overload

≥ 105% ~ 110% for 1 h,

≥ 110% ~ 125% for 10 min,

≥ 125% ~ 150% for 1 min, ≥ 150% shut down in 10 s,

≥ 200% shut down immediately
Shortcircuit
Current-limiting, shut down immediately until the user start up
Max. efficiency
≥ 90%
≥ 91%
≥ 92%
≥ 93%
BYPASS
Rated voltage
380 Vac three-phase + N+PE
Voltage range
± 20%
Rated frequency
50 Hz / 60 Hz ± 5 Hz
Max. current
22 A
45 A 68 A 90 A 114 A 136 A 227 A 272 A
BATTERIES MANAGEMENT
EOD voltage settings
1.58 Vdc ~ 1.83 Vdc (settable), 1.75 Vdc (default)
Staggering DOD (Depth of Discharge) settings
1.85 Vdc ~ 2.1 Vdc (settable), 1.89 Vdc (default)
Charging current settings
Factory default 0.15 C10; 0.07 ~ 0.3 C10(settable)
Battery management
Auto-transfer between equalizing charge and floating charge; Auto- temperature compensation of batteries
TRANSFER TIME
Inverter – Bypass
0 ms
Bypass – Inverter
0 ms
COMMUNICATIONS
Remote control
Inverter startup, shutdown, abnormal clearance, EPO, battery self-test
Communication interface
RS232 / RS485 (standard); SNMP / Wi-Fi / GPRS (optional)
Dry contacts output 
Bypass input abnormal, rectifier input abnormal, system fault, system alarm, low battery, output overload, fan fault, generator ON / OFF
OTHERS
Operating temperature
0℃~ 40℃
Max. relative humidity
90% (non-condensing)
Max. altitude
1000 m at rated power (derating 1% for each additional 100 m); Max. 4000 m
Noise level at 1 m
≤ 65 dB (varies with loads and temperature)
IP rating
IP20
Dimensions (W × D × H) (mm)
450 × 840 × 1100
600 × 700 × 1750
960 ×800 × 1700
Packaged dimensions (W×D×H) (mm)
560 × 940 × 1300
700 × 800 × 1950
1060 × 900 × 1900
Weight (kg)
230 245 380 430 515 848 854 860

● All specifications subject to change without notice.