EAST stock code: 300376

MC6000

Characteristics Technical Specifications Documents

Reliability

Ÿ  System standardization architecture design makes components and parts high versatile and avoids system design problems

Ÿ  System fault-tolerant design helps high reliability

Ÿ  Strong and weak current separation design makes less electromagnetic interference

Ÿ  Very early fire warning

Ÿ  Pass 8,9 intensity electrified seismic performance test

 

High efficiency

Ÿ  Efficient integrated power supply and distribution, enclosed hot and cold aisles, high power density and energy efficiency

Ÿ  Support single-row or double-row hot-cold aisle containment in a variety of ways, isolate hot and cold air flow and eliminate local hot spots

 

Simplification

Ÿ  Standard modular structure design helps to realize modular combination in different sizes and different powers. Product delivery can be completed in 3-6 weeks

 

Intelligence

Ÿ  Micro-module monitoring system performs all-round monitoring and unified management on the power distribution, environment, security, fire protection and other equipment inside the micro-module

Ÿ  Energy consumption of the micro-module can be analyzed precisely through the precise distribution system

 

Energy conservation

Ÿ  PUE can be maintained at a lower level through enclosed aisle design, and is more energy efficient than traditional computer room

Ÿ  Later expansion available, saving investment costs


Micro modular   system

Dimensions

Single row cold / hot   aisle containment (L×W×H)

L×2465×2550/2750   mm, L ≤ 15 m

L×2365×2550/2750   mm, L ≤ 15 m

L×2265×2550/2750   mm, L ≤ 15 m

Double row cold / hot   aisle containment (L×W×H)

L×3600×2550/2750   mm, L ≤ 15 m

L×3400×2550/2750   mm, L ≤ 15 m

L×3200×2550/2750   mm, L ≤ 15 m

Access doors

Revolving sliding   door (concealed door closer, concealed electromagnetic locks design; two   installations - access inside / outside are selectable for the power and   environment monitoring display screen)

Translation door   (auto / manual are selectable)

Cabinet quantities   of Single module

Single row: 3 - 24

Double row: 6 - 48

Power   mode

AC: 380/400/415 Vac,   50 / 60 Hz, 3Ph + N + PE

DC: - 48 / 240 /   336 Vdc

Single   module IT power consumption

Max. 200kW  (Confirm with an engineer for above 200kW)

Max. power of   single cabinet

18 kW

Operating   environment

Ultra-low   temperature condition: -40 ~ 45

T1 condition: -25 ~   45

T3 condition: -5 ~   45

Reliability level

Tier II or Tier III   (extendable to Tier IV)

Altitude

0 - 1000 m   (downgrading for above 1000 m)

Cabinet

Dimensions (W×D×H)

600/800×1200×2000/2200   mm

600/800×1100×2000/2200   mm

600/800×1000×2000/2200   mm

Available space

42 U / 47 U

IP rating

IP 20

Air cooled in-row   air conditioner

Refrigerating capacity

12 kW / 25 kW / 40   kW

Dimensions of   internal machine

300/600×1000/1100/1200×2000/2200   mm

Input power supply

AC: 380/400/415 Vac,   50 / 60 Hz

(optional DC:   240/336 Vdc)

Refrigerant

R410A

Fluorine pump

Optional

Chilled water   in-row air conditioner

Refrigerating   capacity

12 kW ~ 70 kW

Dimensions of   internal machine

300/600×1000/1100/1200×2000/2200   mm

Input power supply

AC: 380/400/415 Vac,   50 / 60 Hz

(optional DC:   240/336 Vdc)

Refrigerant

Water / ethylene   glycol aqueous solution

Integrated UPS

(built-in UPS)

Input voltage

380/400/415 Vac, 50   / 60 Hz, 3Ph + N + PE

Input   power factor

> 0.99 (full   load), > 0.98 (half load)

Rated   capacity

50 ~ 200 kVA

Efficiency

≥ 96%

AC lightning   protection

Class B, C

Modular power distribution   cabinet (external UPS)

Input voltage

380/400/415 Vac, 50   / 60 Hz, 3Ph + N + PE

Rated   capacity

500 A

AC lightning   protection

Class B, C


MC 6000 Datasheet - PDF



 
Online Support