EA600 500-3000VA
● Pure sine wave output
● DSP digital control
● Boost and buck AVR for voltage stabilization
● Auto sensing frequency
● Adjustable charging current and battery shutdown point
● Settable ECO mode and no-load shutdown
● Humanized alarm system
● Power-on self test
● Cold start
● Auto restart when mains power is restored
● Intelligent battery management
● Short circuit and overload protection
● Automatic charging in OFF mode
● USB & RJ45, AS400 / SNMP (optional) communication port
MODEL | EA605 | EA610 | EA615 | EA620 | EA630 | |
Capacity | 500VA / 300W | 1000VA / 800W | 1500VA / 1200W | 2000VA / 1600W | 3000VA / 2400W | |
DC INPUT | ||||||
Rated voltage | 12 V | 24 V | 36 V (S) | 48 V | ||
DC input range (default) | 10 ~ 15 V | 20 ~ 30 V | 30 ~ 45 V (S) | 40 ~ 60 V | ||
AC INPUT | ||||||
AC input range (bypass mode) | 0 ~ 121 / 132 / 138 / 144 Vac for 100 / 110 / 115 / 120 Vac ± 10 Vac 0 ~ 242 / 264 / 276 / 288 Vac for 200 / 220 / 230 / 240 Vac ± 10 Vac | |||||
AC input range (mains mode) | 100 V: 70 ~ 130 Vac 110 V: 80 ~ 140 Vac 115 V: 85 ~ 145 Vac | |||||
Frequency input range | 50 Hz / 60 Hz (auto-sense), 50 Hz / 60 Hz ± 5% ~ 15% | |||||
Generator connection | Available (generator input power is settable) | |||||
OUTPUT | ||||||
Inverter output range | 100 / 110 / 115 / 120 / 200 / 220 / 230 / 240 Vac ± 5% (settable) | |||||
AC output range (bypass mode) | 0 ~ 121 / 132 / 138 / 144 Vac for 100 / 110 / 115 / 120 Vac ± 10 Vac
0 ~ 242 / 264 / 276 / 288 Vac for 200 / 220 / 230 V / 240 Vac ± 10 Vac | |||||
AC output range (mains mode) | 100 V: 90 ~ 110 Vac 110 V: 99 ~ 121 Vac 115 V: 103 ~126 Vac | |||||
Output frequency | 50 / 60 Hz ± 0.3 Hz (settable) | |||||
Waveform | Pure sine wave | |||||
Inverter efficiency | Max. 75% | Max. 80% | Max. 85% | |||
Energy saving mode | Settable (< 3% load), enter in 80 s | |||||
No-load shutdown | Settable (< 3% load), shut down in 80 s | |||||
Transfer time | ≤ 10 ms | |||||
THDV | ≤ 5% | |||||
Protections | Overload, short circuit (inverter), battery low voltage, battery overcharge, overtemperature | |||||
Overload (mains mode) | 110% for 120 s, 125% for 60 s, 150% for 10 s (transfer to bypass mode) | |||||
Overload (inverter mode) | 110% for 60 s, 125% for 10 s, 150% for 5 s (shut down directly) | |||||
Mute | Automatic mute in 60s or by manual | |||||
BATTERIES | ||||||
Inbuilt battery (standard model) | / | 12 V / 7 Ah x 2 | 12 V / 9 Ah x 2 | 12 V / 9 Ah x 3 | 12 V / 9 Ah x 4 | |
Charging current | Standard model (S): 1 A (default) | |||||
Long time model (H): 10 A (default); < 10 A, set step 1 A; ≥ 10 A, set step 5 A | ||||||
Max. 10 A (H) | Max. 15 A (H) | / | Max. 20 A (H) | Max. 25 A (H) | ||
Equalizing | Single battery 14.1 Vdc (default), 13.6 ~ 15 Vdc adjustable | |||||
Floating charge voltage | Single battery 13.5 Vdc (default),13.2 ~ 14.6 Vdc adjustable | |||||
Low voltage alarm point | Single battery 10.8 Vdc (default), 9.6 ~ 13 Vdc adjustable | |||||
Low voltage shutdown point | Single battery 10.2 Vdc (default), 9.6 ~ 11.5 Vdc adjustable | |||||
OTHERS | ||||||
Communications | USB & RJ45
(standard), dry contacts / SNMP (optional) | |||||
Operating temperature | 5℃ ~ 40℃ | |||||
Operating humidity | Relative humidity ≤ 93% | |||||
Noise level | ≤ 50 dB (1 m) | |||||
Tower | Dimensions (W × D × H) (mm) | 144 x 345 x 215 (S / H) | 144 x 410 x 215 (S) |
157.5 x 460x 221.5(S) 190 x 467 x 335.5 (H) | ||
Packaged dimensions (W × D × H) (mm) | 236 x 427 x 316 (S / H) | 236 x 492 x 316 (S) | 238 x 550 x 305 (S) 320 x 592 x 462 (H) | |||
Net weight (kg) | 7.0 (H) | 12.2 (S) | 14.2 (S) | 18.5 (S) | 23.6(S) 28.0 (H) | |
Gross weight (kg) | 8.0 (H) | 13.2 (S) | 15.2 (S) | 19.8 (S) | 25 (S) | |
Rack mount | Dimensions (W × D × H) (mm) | -- | 440 × 338 × 88 (S) | 440 × 410 × 132 (S) | ||
Packaged dimensions (W × D × H) (mm) | -- | 611 × 448 × 208 (S) | 611 × 505 × 235 (S) | |||
Net weight (kg) | -- | 14.6 (S) | 17.2 (S) | 21.3 (S) | 26.7 (S) | |
Gross weight (kg) | -- | 16.8 (S) | 20.4 (S) | 24.5 (S) | 30.5 (S) |