MC6000

Characteristics Technical Specifications Documents

Reliability

Ÿ  System standardization architecture design makes components and parts high versatile and avoids system design problems

Ÿ  System fault-tolerant design helps high reliability

Ÿ  Strong and weak current separation design makes less electromagnetic interference

Ÿ  Very early fire warning (option)

Ÿ  Pass 8,9 intensity electrified seismic performance test

 

High efficiency

Ÿ  Efficient integrated power supply and distribution, enclosed hot and cold aisles, high power density and energy efficiency

Ÿ  Support single-row or double-row hot-cold aisle containment in a variety of ways, isolate hot and cold air flow and eliminate local hot spots

 

Simplification

Ÿ  Standard modular structure design helps to realize modular combination in different sizes and different powers. Product delivery can be completed in 3-6 weeks

 

Intelligence

Ÿ  Micro-module monitoring system performs all-round monitoring and unified management on the power distribution, environment, security, fire protection and other equipment inside the micro-module

Ÿ  Energy consumption of the micro-module can be analyzed precisely through the precise distribution system

 

Energy conservation

Ÿ  PUE can be maintained at a lower level through enclosed aisle design, and is more energy efficient than traditional computer room

Ÿ  Later expansion available, the capacity can be gradually upgraded and expanded according to the later development situation, saving the initial investment cost.


Micro modular system

Dimensions

Single row cold / hot aisle containment (L×W×H)

L×2465×2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped

L×2365×2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped

L×2265×2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped

Double row cold / hot aisle containment (L×W×H)

L×3600×2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped

L×3400×2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped

L×3200×2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped

Access doors

Revolving sliding door (concealed door closer, concealed electromagnetic locks design; two installations - access inside / outside are selectable for the power and environment monitoring display screen)

Translation door (auto / manual are selectable, with 200mm deep cabinets on both sides, can hide the translation door, and can install dynamic environment equipment)

Cabinet quantity of Single module

Single row: 3 - 24

Double row: 6 - 48

Power mode

AC: 380/400/415 Vac, 50/60 Hz, 3Ph+N+PE

DC: -48/240/336Vdc, positive and negative+PE

Single module IT power consumption

Max. 200kW (Confirm with an engineer for above 200kW)

Max. power of single cabinet

18kW

Operating environment

Ultra-low temperature condition: -40~45

T1 condition: -25~45

T3 condition: -5~45

Reliability level

Tier II or Tier III (extendable to Tier IV)

Altitude

0-1000m (derating for above 1000m)

Cabinet

Dimensions (W×D×H)

600/800×1200×2000/2200mm

600/800×1100×2000/2200mm

600/800×1000×2000/2200mm

Available space

42U / 47U

IP rating

IP20

Air cooled in-row air conditioner

Refrigerating capacity(single air conditioner)

12kW / 25kW / 40kW

Dimensions of internal machine

300/600×1000/1100/1200×2000/2200mm

Input power supply

AC: 380/400/415Vac, 50/60Hz

(optional DC: 240/336Vdc)

Refrigerant

R410A

Fluorine pump

Optional

Chilled water in-row air conditioner

Refrigerating capacity

12kW~70kW

Dimensions of internal machine

300/600×1000/1100/1200×2000/2200mm

Input power supply

AC: 380/400/415Vac, 50/60Hz

(optional DC: 240/336Vdc)

Refrigerant

Water / ethylene glycol aqueous solution

Integrated UPS

(built-in UPS)

Input voltage

380/400/415Vac, 50/60Hz, 3Ph+N+PE

Input power factor

>0.99 (full load), >0.98 (half load)

Rated capacity

50~200kVA

Efficiency

≥96%

AC lightning protection

Class B, C

Modular power distribution cabinet (external UPS)

Input voltage

380/400/415Vac, 50/60Hz, 3Ph+N+PE

Rated capacity

500A

AC lightning protection

Class B, C


MC6000 Datasheet - PDF