MC6000
Reliability
System standardization architecture design makes components and parts high versatile and avoids system design problems
System fault-tolerant design helps high reliability
Strong and weak current separation design makes less electromagnetic interference
Very early fire warning (option)
Pass 8,9 intensity electrified seismic performance test
High efficiency
Efficient integrated power supply and distribution, enclosed hot and cold aisles, high power density and energy efficiency
Support single-row or double-row hot-cold aisle containment in a variety of ways, isolate hot and cold air flow and eliminate local hot spots
Simplification
Standard modular structure design helps to realize modular combination in different sizes and different powers. Product delivery can be completed in 3-6 weeks
Intelligence
Micro-module monitoring system performs all-round monitoring and unified management on the power distribution, environment, security, fire protection and other equipment inside the micro-module
Energy consumption of the micro-module can be analyzed precisely through the precise distribution system
Energy conservation
PUE can be maintained at a lower level through enclosed aisle design, and is more energy efficient than traditional computer room
Later expansion available, the capacity can be gradually upgraded and expanded according to the later development situation, saving the initial investment cost.
Micro modular system | Dimensions | Single row cold / hot aisle containment (L×W×H) |
L×2465×2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped | ||
L×2365×2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped | ||
L×2265×2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped | ||
Double row cold / hot aisle containment (L×W×H) | ||
L×3600×2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped | ||
L×3400×2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped | ||
L×3200×2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped | ||
Access doors | Revolving sliding door (concealed door closer, concealed electromagnetic locks design; two installations - access inside / outside are selectable for the power and environment monitoring display screen) | |
Translation door (auto / manual are selectable, with 200mm deep cabinets on both sides, can hide the translation door, and can install dynamic environment equipment) | ||
Cabinet quantity of Single module | Single row: 3 - 24 Double row: 6 - 48 | |
Power mode | AC: 380/400/415 Vac, 50/60 Hz, 3Ph+N+PE | |
DC: -48/240/336Vdc, positive and negative+PE | ||
Single module IT power consumption | Max. 200kW (Confirm with an engineer for above 200kW) | |
Max. power of single cabinet | 18kW | |
Operating environment | Ultra-low temperature condition: -40~45℃ | |
T1 condition: -25~45℃ | ||
T3 condition: -5~45℃ | ||
Reliability level | Tier II or Tier III (extendable to Tier IV) | |
Altitude | 0-1000m (derating for above 1000m) | |
Cabinet | Dimensions (W×D×H) | 600/800×1200×2000/2200mm |
600/800×1100×2000/2200mm | ||
600/800×1000×2000/2200mm | ||
Available space | 42U / 47U | |
IP rating | IP20 | |
Air cooled in-row air conditioner | Refrigerating capacity(single air conditioner) | 12kW / 25kW / 40kW |
Dimensions of internal machine | 300/600×1000/1100/1200×2000/2200mm | |
Input power supply | AC: 380/400/415Vac, 50/60Hz (optional DC: 240/336Vdc) | |
Refrigerant | R410A | |
Fluorine pump | Optional | |
Chilled water in-row air conditioner | Refrigerating capacity | 12kW~70kW |
Dimensions of internal machine | 300/600×1000/1100/1200×2000/2200mm | |
Input power supply | AC: 380/400/415Vac, 50/60Hz (optional DC: 240/336Vdc) | |
Refrigerant | Water / ethylene glycol aqueous solution | |
Integrated UPS (built-in UPS) | Input voltage | 380/400/415Vac, 50/60Hz, 3Ph+N+PE |
Input power factor | >0.99 (full load), >0.98 (half load) | |
Rated capacity | 50~200kVA | |
Efficiency | ≥96% | |
AC lightning protection | Class B, C | |
Modular power distribution cabinet (external UPS) | Input voltage | 380/400/415Vac, 50/60Hz, 3Ph+N+PE |
Rated capacity | 500A | |
AC lightning protection | Class B, C |