MC6000
Reliability
System standardization architecture design makes components and parts high versatile and avoids system design problems
System fault-tolerant design helps high reliability
Strong and weak current separation design makes less electromagnetic interference
Very early fire warning
Pass 8,9 intensity electrified seismic performance test
High efficiency
Efficient integrated power supply and distribution, enclosed hot and cold aisles, high power density and energy efficiency
Support single-row or double-row hot-cold aisle containment in a variety of ways, isolate hot and cold air flow and eliminate local hot spots
Simplification
Standard modular structure design helps to realize modular combination in different sizes and different powers. Product delivery can be completed in 3-6 weeks
Intelligence
Micro-module monitoring system performs all-round monitoring and unified management on the power distribution, environment, security, fire protection and other equipment inside the micro-module
Energy consumption of the micro-module can be analyzed precisely through the precise distribution system
Energy conservation
PUE can be maintained at a lower level through enclosed aisle design, and is more energy efficient than traditional computer room
Later expansion available, saving investment costs
Micro modular system | Dimensions | Single row cold / hot aisle containment (L×W×H) |
L×2465×2550/2750 mm, L ≤ 15 m | ||
L×2365×2550/2750 mm, L ≤ 15 m | ||
L×2265×2550/2750 mm, L ≤ 15 m | ||
Double row cold / hot aisle containment (L×W×H) | ||
L×3600×2550/2750 mm, L ≤ 15 m | ||
L×3400×2550/2750 mm, L ≤ 15 m | ||
L×3200×2550/2750 mm, L ≤ 15 m | ||
Access doors | Revolving sliding door (concealed door closer, concealed electromagnetic locks design; two installations - access inside / outside are selectable for the power and environment monitoring display screen) | |
Translation door (auto / manual are selectable) | ||
Cabinet quantities of Single module | Single row: 3 - 24 Double row: 6 - 48 | |
Power mode | AC: 380/400/415 Vac, 50 / 60 Hz, 3Ph + N + PE | |
DC: - 48 / 240 / 336 Vdc | ||
Single module IT power consumption | Max. 200kW (Confirm with an engineer for above 200kW) | |
Max. power of single cabinet | 18 kW | |
Operating environment | Ultra-low temperature condition: -40 ~ 45℃ | |
T1 condition: -25 ~ 45℃ | ||
T3 condition: -5 ~ 45℃ | ||
Reliability level | Tier II or Tier III (extendable to Tier IV) | |
Altitude | 0 - 1000 m (downgrading for above 1000 m) | |
Cabinet | Dimensions (W×D×H) | 600/800×1200×2000/2200 mm |
600/800×1100×2000/2200 mm | ||
600/800×1000×2000/2200 mm | ||
Available space | 42 U / 47 U | |
IP rating | IP 20 | |
Air cooled in-row air conditioner | Refrigerating capacity | 12 kW / 25 kW / 40 kW |
Dimensions of internal machine | 300/600×1000/1100/1200×2000/2200 mm | |
Input power supply | AC: 380/400/415 Vac, 50 / 60 Hz (optional DC: 240/336 Vdc) | |
Refrigerant | R410A | |
Fluorine pump | Optional | |
Chilled water in-row air conditioner | Refrigerating capacity | 12 kW ~ 70 kW |
Dimensions of internal machine | 300/600×1000/1100/1200×2000/2200 mm | |
Input power supply | AC: 380/400/415 Vac, 50 / 60 Hz (optional DC: 240/336 Vdc) | |
Refrigerant | Water / ethylene glycol aqueous solution | |
Integrated UPS (built-in UPS) | Input voltage | 380/400/415 Vac, 50 / 60 Hz, 3Ph + N + PE |
Input power factor | > 0.99 (full load), > 0.98 (half load) | |
Rated capacity | 50 ~ 200 kVA | |
Efficiency | ≥ 96% | |
AC lightning protection | Class B, C | |
Modular power distribution cabinet (external UPS) | Input voltage | 380/400/415 Vac, 50 / 60 Hz, 3Ph + N + PE |
Rated capacity | 500 A | |
AC lightning protection | Class B, C |