EAST stock code: 300376

EA900RT G3 1-3kVA (120V)

Characteristics Technical Specifications Documents

l  High frequency on-line double conversion technology

l  DSP (Digital signal processing) control technology

l  Active power factor correction (APFC), input power factor up to 0.99

l  Output power factor 0.9/1.0

l  Wide input voltage range (50V ~ 150Vac) and frequency range (40 ~ 70 Hz)

l  Auto sensing frequency

l  50 / 60 Hz frequency conversion

l  Cold start

l  Rear ventilation design and variable speed fan

l Effective software and hardware protection

l  Quick and stable charging, 90% capacity restored in 3h (standard model UPS)

l  Linear derating in low voltage input reducing battery discharging times

l Settable delayed start when power is restored

l Advanced battery management (ABM)

l  Multiple functions settable via LCD: output voltage, EOD, auto-start, bypass mode

l  Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)

l  Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, EPO function; MBS (External maintenance bypass switch)

MODEL

EA901RT

EA902RT

EA903RT

Capacity

1kVA / 1kW

2kVA / 2kW

3kVA / 3kW

INPUT

Rated voltage

100 /110 /115 /120 /127 Vac

Voltage range

50 ~ 80Vac (linear   derating between 50% and 100% load); 80 ~ 150Vac (no derating)

Frequency range

40~70 Hz(auto-sensing)

Power factor

≥0.99

Bypass voltage range

- 25% ~ +15% (settable)

Rated input frequency

50 Hz / 60 Hz (auto-sense)

THDi

≤6%

OUTPUT

Voltage

100 /110 /115 /120 /127 Vac(settable via LCD)

Voltage regulation

± 1%

Frequency

45~55Hz or 55~65Hz(synchronized range); 50/60Hz ±0.1Hz (battery mode)

Waveform

Sinusoidal

Power factor

0.9/1.0

THDv

≤2% (linear load), ≤5% (non-linear load)

Crest factor

3:1

Overload

108% ~ 127% for 1 min, 127% ~ 150% for 30 s, > 150% for 100 ms

BATTERIES

Battery type

Sealed lead acid maintenance free battery

DC voltage

24V

48V

72V

Inbuilt battery

2 × 9 Ah

4 × 9 Ah

6 × 9 Ah

Charging current   (max.)

1 A

Recharge time

Standard model: 90% capacity restored in 3 hours

SYSTEM

Efficiency

≥ 90% (Mains mode)

≥ 85% (Battery mode)

≥ 95% (ECO mode)

Transfer time

Mains mode to battery mode: 0 ms
  Inverter mode to bypass mode: 4 ms (typical)

Protections

Short-circuit, overload, overtemperature, battery discharge protection and fan testing protection

Communication port

RS232 (standard), USB / RS485 / SNMP/ dry contacts (optional)

Display

LCD + LED

ENVIRONMENTAL

Operating humidity

0 ~ 95 % RH @ 0 ~ 40°C (non-condensing)

Storage temperature

-25°C ~  55°C (exclude batteries)

Operating altitude

≤1000m, above 1000m, derating 1% for each additional 100 m

IP rating

IP 20

Noise level at 1m

≤ 50 dB

OTHERS

Dimensions (W×D×H) (mm)

440×316×88

440×468×88440×560×88

Packaged dimensions (W×D×H) (mm)

545×428×194

545×592×198545×690×201

Net weight (kg)

10.8

16.324

Gross weight (kg)

11.5

19.827

* Derate capacity to 70% in CUCF mode and to 90% when the output voltage is adjusted to 100Vac.

* S means standard model, H means long time model.

* All specifications are subject to change without notice.

* Custom-made specifications are acceptable.

EA900RT G3 1-3kVA (120V) Datasheet - PDF

 