EAST stock code: 300376

EA900 G3 1-3kVA

Characteristics Technical Specifications Documents

  • High frequency on-line double conversion technology

  • DSP (Digital signal processors) control technology

  • Active power factor correction (APFC), input power factor up to 0.99

  • Output power factor 0.9/1.0

  • Wide input voltage range (110 V ~ 300 Vac) and frequency range (40 ~ 70 Hz)

  • Auto sensing frequency

  • 50 / 60 Hz frequency conversion

  • Cold start

  • Rear ventilation design and variable speed fan

  • Effective software and hardware protection

  • Quick and stable charging, 90% capacity restored in 3h (standard model UPS)

  • Linear derating in low voltage input reducing battery discharging times

  • Settable delayed start when power is restored

  • Advanced battery management (ABM)

  • Multiple functions settable via LCD: output voltage, EOD, auto-start, bypass mode

  • Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)

  • Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, EPO function

MODELEA901EA902EA903
Capacity1kVA / 1kW2kVA / 2kW3kVA / 3kW
INPUT
Rated voltage208 / 220 / 230 / 240Vac
Voltage range110 ~ 176Vac (linear derating between 50% and 100% load ); 176 ~ 280Vac (no derating); 280 ~ 300Vac (derating 50%)
Frequency40 ~ 70Hz (auto-sensing)
Power factor≥0.99
Bypass voltage range- 25% ~ +15% (settable)
Total harmonic distortion (THDi)
≤ 6%
OUTPUT
Voltage208 / 220 / 230 / 240Vac (settable via LCD)
Voltage regulation±1%
Frequency45 ~ 55Hz or 55 ~ 65Hz (synchronized range); 50 / 60Hz ± 0.1Hz (battery mode)
WaveformSinusoidal
Power factor0.9/1.0
Total harmonic distortion (THDv)≤2% (linear load), ≤5% (non-linear load)
Crest factor3:1
Overload105% ~ 125% for 1min, 125% ~ 150% for 30s, >150% for 300ms
BATTERIES
DC voltage24V(S)24V(H)36V(S)36V(H)48V(S)48V(H)72V(S)72V(H)72V(S)72V(H)96V(S)96V(H)
Inbuilt battery 2×9Ah/3×7Ah/4×9Ah/6×7Ah/6×9Ah/8×7Ah/
Charging current (max.)Standard model: 1A, long time model: 6A
Recharge timeStandard model: 90% capacity restored in 3 hours; Long time model: depend on the capacity of battery
   
SYSTEM
Efficiency≥90% (Mains mode)
≥91% (Mains mode)  ≥92% (Mains mode)
≥85% (Battery mode)≥86% (Battery mode)≥87% (Battery mode)
≥95% (ECO mode)≥96% (ECO mode)≥97% (ECO mode)
Transfer timeMains mode to battery mode: 0 ms
    Inverter mode to bypass mode: 4 ms (typical)   
ProtectionsShort-circuit, overload, overtemperature, battery discharge protection and fan testing protection
CommunicationsRS232 (standard), USB / RS485 / dry contacts / SNMP (optional)
DisplayLCD + LED
StandardsEN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2, IEC 62040-2, IEC 62040-1, IEC 62040-3
OTHERS
Operating temperature0℃ ~ 40℃
Storage temperature-25°C ~ 55°C (without batteries)
Relative humidity0 ~ 95% (non-condensing)
Altitude≤ 1000m, derating 1% for each additional 100 m
IP ratingIP 20
Noise level at 1m≤ 50dB 

Dimensions

(W×D×H) (mm)

144×312×216144×336×214144×371×216144×336×216144×417×216191×418×335191×419×335191×418×335191×419×335191×418×335191×419×335191×418×335

Packaged dimensions (W×D×H) (mm)

230×402×315232×417×318
230×460×315232×417×318230×506×315277×500×435318×533×471277×500×435277×500×435
Net weight (kg)116
12.8616.410.523.110.524.31129.411
Gross weight (kg)
11.36.914717.811.624.71225.912.531.112.5


EA900 G3 1-3kVA Datasheet - PDF

EA900 G3 1-3kVA User Manual - PDF



 
Online Support