MC2000
Simplification
MC2000 overall system standard modular structure design, each sub-module is highly versatile. The sub-modules of MC2000 are prefabricated by factory and can be assembled on site, which has low requirement for installation place. The equipment can be put into use immediately after the arrival. In the process of utilization, it only needs one monitoring and management system during use with no need of facing multiple interfaces.
High efficiency
MC2000 has three types of aisle containment: hot-cold aisle containment (recommended), cold aisle containment and natural cooling. Thereinto, cold aisle containment can significantly improve the utilization of cooling capacity, hot aisle containment can improve the refrigerating efficiency of air conditioner, hot-cold aisle containment can improve the utilization of colling capacity as well as the refrigerating efficiency of air conditioner. Its PUE (Power Usage Effectiveness) is industry-leading.
Flexibility
Overall system standard modular structure design, each sub-module is highly versatile. Multiple solutions can be implemented by combining them as needed.
The later stage can realize expansion easily.
Reliability
Adopts hot-cold aisle containment, cold aisle containment and natural cooling to adapt to multiple environments.
Overall system standard modular structure design can avoid system design problems.
System fault-tolerant design helps high reliability.
Strong and weak current separation design can make less electromagnetic interference.
Pass 8,9 intensity electrified seismic performance test
Intelligence
MC2000 has built-in monitoring and management system and is configured with 10.1-inch industrial touch screen that can be used not only to view the parameters of the power supply and distribution, air conditioner, environmental variable and UPS but also to remotely monitor the operating parameters inside MC2000. Moreover, it can be connected to the superior monitoring platform via the internet for multi-network centralized monitoring and efficient management.
The MC2000 cabinet is equipped with intelligent LED ambient lights. When the temperature is 18-27°C, the light will be blue (normal work). When the temperature exceeds 27°C, the color of the light will gradually change from yellow to red (warning effect). When the front door is opened, the white light is on for operation and maintenance. At the same time, the LED ambient light is linked with the infrared sensor on the top of the cabinet. When the infrared sensor detects that a person is approaching the device, the smart LED ambient light starts up normally, and automatically turns off after 5 minutes away from the device.
Overall system parameters | Number of cabinets for single module | 1 - 12 |
Max. available space | 420 U (12 cabinets, without battery pack, 54 kW load) | |
Aisle type | Single row aisle, natural cooling / cold aisle containment / hot-cold aisle containment | |
Power density range | 3 - 8 kW / cabinet | |
Battery deployment | Battery pack, battery cabinet, battery rack | |
Battery backup time | 15 min - 240 min | |
Installation | Concrete ground, raised flooring | |
Power mode | Single-phase three-wire / three-phase five-wire | |
System protection grade | IP 20 (mesh door) / IP 50 (glass door) | |
Operating temperature | -20℃ ~ 45℃ | |
Altitude | Derating for above 1000 m | |
Cabinet system | Natural cooling | (N×600)×1200×2000 mm (excluding casters and adjusting feet, front and rear high density ventilation mesh doors; N is cabinet quantity) |
Cold aisle containment | (N×600)×1200×2000 mm (excluding casters and adjusting feet, front glass door and rear mesh door; N is cabinet quantity) | |
Hot-cold aisle containment | (N×600)×1400×2000 mm (excluding casters and adjusting feet, front and rear glass doors; N is cabinet quantity) | |
IP rating | IP 20 (mesh door) / IP 50 (glass door) | |
Refrigeration system | Input power supply | 220 Vac |
Refrigerating capacity | 4.5 kW (4U) / 8 kW (10U) / 15 kW (12U) / 30 kW (21U) | |
Air conditioner configuration | 1+0, 1+1, 2+0, 2+1, 3+0, 3+1 (optional) | |
Sensible heat factor (sensible cooling capacity / total cooling capacity) | 1 | |
Refrigerant | R410A | |
Air supply method | Supply air in front and return air in the rear | |
Installation | Rack-mounted | |
Power supply and distribution system | Power input | Single-phase three-wire / Three-phase five-wire |
UPS capacity | 3 kVA /6 kVA /10 kVA / 20 kVA | |
UPS configuration | N, N+1 | |
UPS rated input voltage | 220/230/240 Vac single-phase, 380/400/415 Vac three-phase | |
UPS input voltage range | 80 ~ 280 Vac single-phase, 138 ~ 485 Vac three-phase | |
UPS output power factor | 0.8/0.9 | |
UPS rated output voltage | 220/230/240 Vac single-phase, 380/400/415 Vac three-phase | |
UPS overall efficiency | 92% / 95% | |
Maintenance bypass | Support | |
Mains power feed-out ways | 4 ways IT + 4 ways air conditioner and fire-fighting systems / 12 ways IT + 5 ways air conditioner and fire-fighting systems | |
UPS feed-out ways | 4 ways IT / 12 ways IT | |
AC lightning protection | Class B, C | |
Monitoring system | Monitoring system host | Support direct access for embedded Web |
Local interface | 10.1-inch industrial touch screen | |
Water leak detection rope | Standard configuration | |
Smoke detection | Standard configuration | |
Temperature and humidity | Standard configuration | |
Automatic spring door device | Optional configuration | |
Door sensor | Optional configuration | |
Power supply and distribution / UPS / air conditioner monitoring | Standard configuration | |
Northbound communication interface | Optional configuration | |
Protocol format | SNMP | |
SMS alarm | Optional configuration | |
Rechargeable fan | Optional configuration | |
Rope light in cabinet | Standard configuration | |
Firefighting system | Heptafluoropropane gas fire protection module | 1U rack installation, a single module can manage two cabinets (optional) |