All-in-one Sodium-ion Battery UPS 6kVA-40kVA
High reliability
l Sodium-ion battery module is equipped with PACK level fire protection as standard configuration, and optional cabinet-level fire protection system, which is safer and more reliable than the lithium-ion battery
l Modular design, fault modules exit automatically, will not affect the normal operation of other modules of the system, improve reliability
l Sodium-ion battery does not smoke, catch fire, or explode during the nail penetration test, and it does not catch fire or burn after short-circuit, overcharge, over-discharge, extrusion or other experiments, so the safety is significantly better than that of a lithium-ion battery
l The sodium-ion battery module adopts 16S1P no parallel mode, no circulating current, and adopts DC/DC boost mode to improve system reliability
High availability
l Sodium-ion battery modular design, easy to replace, high maintainability, to achieve higher power density integration and miniaturization
l The all-in-one sodium-ion battery UPS is flexible in configuration and can expand the capacity of modules or cabinets according to the UPS capacity
l It adopts a high-security intelligent BMS system, which can be configured with HMI monitoring and intelligent visualization management
l Small footprint and high energy density, saving 70% of footprint compared to lead-acid battery
l High rate charging - supports 1H high-speed charging, saving more than 80% charging time compared to lead-acid battery
l The UPS can be started directly with the battery in the absence of mains to meet emergency requirements
l The conversion time of the UPS power supply mode is zero when the mains is unstable, which guarantees that the output will not break down
High intelligence
l The sodium-ion battery module is equipped with fault self-recovery, real-time equalization function of the battery cells, and provides overvoltage, undervoltage, overcurrent, short-circuit, high and low temperatures and other protection functions, which improves the reliability of the module and increases the life of the battery
l Intelligent charge and discharge management to avoid overcharge and over-discharge
l The sodium-ion battery module automatically detects the internal temperature of the battery, which has better thermal stability and reliability
Energy-saving and environmentally friendly
l Compared with lead-acid and lithium-ion batteries, sodium-ion batteries do not contain toxic and harmful substances, and have less impact on the environment, which is more environmentally friendly
l The UPS control utilizes active power factor correction (PFC) technology with an input power factor of up to 0.99
Warranty
l Promised 5-year warranty
MODEL | EA906/9010YN | EA9010/9015/9020YN | EA9910/9920YN | EA9930/9940YN | |||||
Rated capacity | 6KVA | 10KVA | 10KVA | 15KVA | 20KVA | 10KVA | 20KVA | 30KVA | 40KVA |
INPUT | |||||||||
Input phases | Single-phase three-wire (1Φ+N+PE) | Three-phase five-wire (3Φ+N+PE) | Three-phase five-wire(3Φ+N+PE) | ||||||
Input rated voltage | 208/220/240Vac | 380/400/415Vac | 380/400/415Vac | ||||||
Input rated frequency | 50/60Hz | 50/60Hz | 50/60Hz | ||||||
Input voltage range | 110~176Vac (linear derating between 50%~100% load) 176~288Vac (No derating) | 190~304Vac (linear derating between 50%~100% load) 304~478Vac (No derating) | 228~304Vac (linear derating between 50%~100% load) 304~478Vac (No derating) | ||||||
Input frequency range | 40Hz~70Hz | ||||||||
Input power factor | >0.99 | ||||||||
Input current THDi | <5% (linear load) | <3% (linear load) | |||||||
Battery module voltage | 240VDC | ||||||||
OUTPUT | |||||||||
Output phases | Single-phase three-wire (1Φ+N+PE) | Three-phase five-wire (3Φ+N+PE) | |||||||
Output rated voltage | 208/220/230/240Vac | 380/400/415Vac | |||||||
Output rated frequency | 50/60Hz | 50/60Hz | |||||||
Output power factor | ≥0.99 | ||||||||
Output voltage accuracy | ±1% (linear load) | ||||||||
Output frequency accuracy | 50/60Hz±0.1% | ||||||||
Output THDu | THD <1% (linear load), THD <4% (non-linear load) | THD <1% (linear load), THD < 3% (non-linear load) | |||||||
Overload capacity | 105%~110%, 10 minutes; 110%~125%,1 minute; 125%~150%, 30s | <110%, 60 minutes; 110%~125%,10 minutes; 125%~150%, 1 minute; >150%, 200ms | |||||||
SYSTEM | |||||||||
System efficiency | Online mode: 94%; ECO mode: 98% | Online mode: 95%; ECO mode: 98% | Online mode: 96%; ECO mode: 98.5% | ||||||
Switching time | 0 ms | ||||||||
Display | LCD | ||||||||
Communication interface | Standard configuration: RS232, RS485, cold start | ||||||||
Protections | Low battery protection, output overload protection, output short-circuit protection, overtemperature protection etc. | ||||||||
OPERATING ENVIRONMENT | |||||||||
Operating temperature | 0~40℃ | ||||||||
Storage temperature | -25℃~55℃ (without battery) | ||||||||
Relative humidity | 0%~95% (non-condensing) | ||||||||
Noise level at 1m | ≤55dB | ≤58dB | ≤60dB | ≤65dB | |||||
Altitude | Altitude ≤1000m, load derated 1% per 100m above 1000m | ||||||||
OTHERS | |||||||||
Dimension(W×D×H)(mm) | 600×850×1600 | 600×850×2000 | |||||||
Battery pack module number(MAX) | 6 | 8 | |||||||
UPS input power distribution module | Input switch, output switch, maintenance switch, battery switch, lightning protection unit(height 4U) | ||||||||
UPS feed out power distribution module(optional) | 32A1P×1, 16A1P×3 | 32A3P×1, 16A1P×4 | 32A3P×1, 16A1P×4 | 63A3P×1, 32A3P×3, 16A1P×4 |
Sodium-ion battery module technical parameters (EUN24050R15S1P )
MODEL | EUN24050R15S1P | |
Basic parameters | Cathode material | NaFePO4 |
Design life | 10 years | |
Rated capacity | 50AH/2280WH | |
Cooling mode | Forced-air cooling | |
Electrical Characteristics | Output voltage | 240VDC |
Max. output power | 7500W@240V | |
Max. charging current | 8A@270V | |
Start-up time | 50-60S | |
Max. parallel number | CAN:16 units | |
Cycle life | 3000 times (1C, 80% DOD,25℃) | |
Mechanical Properties | Dimension(W×D×H)(mm) | 440×700×160(3U)(without hanging lug) |
Weight | ≤46.5KG | |
Installation type | Standard 19-inch rack | |
Communication interface | CAN/RS485;1pc DO;1pc DI | |
Environments | Operating temperature | 0℃~40℃ no derating, 40℃~50℃ power linear derating to 50% |
Storage temperature | 0℃~55℃ | |
Transport temperature | -40℃~+60℃ | |
Relative humidity | 0%~95% (non-condensing) | |
Altitude | Altitude≤1000m, load derated 1% per 100m above 1000m, up to 5000m |