Hybrid Inverter 3kW-6kW LCD
● Elegant appearance, wall-mounted design, easy installation
● IP66 all-aluminum chassis, adaptable to the outdoor environment
● Off-grid and grid connected dual output, the switching time is less than 20ms
● High charge/discharge efficiency, compatible with lithium battery and lead-acid battery
● Graphical LCD and key design, user-friendly operation interface
● Flexibly settable charge/discharge time section and power, peak load shaving
● APP real time monitoring, easy maintenance
● Outstanding off-grid output performance, adaptable to various non-linear load
| MODEL | EAHI-3000-SL | EAHI-3600-SL | EAHI-5000-SL | EAHI-6000-SL | 
| PV INPUT | ||||
| Max. input power | 4680W | 6500W | 7800W | |
| Max. input voltage | 550Vdc | |||
| Rated input voltage | 360Vdc | |||
| Start-up voltage | 100Vdc | |||
| Min. operating voltage | 150Vdc | |||
| MPPT voltage range | 100~540Vdc | |||
| Max. input current | 16A | 16A | 16A/16A | 16A/16A | 
| Max. short-circuit current | 24A | 24A | 24A/24A | 24A/24A | 
| Number of MPPT | 1 | 1 | 2 | 2 | 
| Number of input strings per MPPT | 1 | 1+1 | ||
| BATTERY INPUT | ||||
| Battery type | Li-ion, Lead-acid battery | |||
| Voltage range | 42~58Vdc | |||
| Max. charge current | 66A | 75A | 100A | 100A | 
| Max. discharge current | 66A | 75A | 100A | 120A | 
| Charging curve | 3 Stages / Equalization | |||
| Lithium battery charging strategy | BMS self-adaption | |||
| AC INPUT(Grid) | ||||
| Grid type | Single phase(L+N+PE) | |||
| Input voltage range | 184~276Vac | |||
| Input frequency range | 50±5Hz/60±5Hz | |||
| Max. input current | 21.8A | 26.2A | 36.5A | 40A | 
| AC OUTPUT(Grid) | ||||
| Rated output power | 3000W | 3600W | 5000W | 6000W | 
| Max. apparent output power | 3000VA | 3600VA | 5000VA | 6000VA | 
| Grid system mode | Single phase(L+N+PE) | |||
| Rated output voltage | 220Vac/230Vac | |||
| Rated output frequency | 50Hz / 60Hz | |||
| Rated output current | 13.6A/13.0 A | 16.4A/15.7A | 22.7A/21.8A | 27.3A/26.1A | 
| Max. output current | 13.6A | 16.4A | 22.7A | 27.3A | 
| Power factor | >0.99 (0.8 leading ~ 0.8 lagging) | |||
| THDI | ≤3% (@ Rated Power) | |||
| AC OUTPUT(Back-up) | ||||
| Rated output power | 3000W | 3600W | 5000W | 6000W | 
| Max. apparent power | 3000VA | 3600VA | 5000VA | 6000VA | 
| Output system mode | Single phase(L+N+PE) | |||
| Rated output voltage | 230Vac (208/220/240Vac settable) | |||
| Rated output frequency | 50Hz/60Hz | |||
| Rated output current@230V | 13.0A | 15.7A | 21.8A | 26.1A | 
| Max. output current | 14.4A | 17.3A | 24.0A | 28.8A | 
| THDV | ≤3% (linear load) | |||
| Transfer time | ≤20ms | |||
| EFFICIENCY | ||||
| Max. efficiency | 97.8% | |||
| MPPT efficiency | 99.9% | |||
| PROTECTIONS | ||||
| Protections | Over/under voltage, over/under-frequency, over load, output short-circuit, over temperature, residual current monitoring unit, output over-current, insulation resistance, anti islanding, surge protection | |||
| Output overvoltage protection | DC Type II/AC Type III | |||
| OTHERS | ||||
| Communications | RS485,WIFI | |||
| Dimensions(W*H*D) | 548x440x197mm | |||
| Net weight | 21.4kg | 24.8kg | ||
| Topology | High frequency isolation(for battery) | |||
| IP rating | IP65 | |||
| Operating temperature | -25℃~+60℃ (>45℃ derating) | |||
| Cooling mode | Natural cooling | |||
| Altitude | 4000m | |||
| Noise level at 1 m | ≤25dB | |||
| Installation mode | Wall hanging | |||
| STANDARDS | ||||
| Safety regulation | IEC/EN 62109-1/-2, AS62109 | |||
| EMC | EN 61000-6-1/-2/-3/-4 | |||
| Grid connection | CEI 0-21, DIN VDE V 0124-100:2020, VDE-AR-N 4105:2018,AS4777.2, NRS097-2-1, EN 50549-1 | |||

 
		 
		 
		 
		 
		 
	